CyberPower OL1500RTXL2UN Smart App Online UPS

BH #CYOL15RTXL2U • MFR #OL1500RTXL2UN
Print
CyberPower OL1500RTXL2UN Smart App Online UPS
Key Features
  • Output: 1500VA / 1350W @ 50/60 Hz
  • Input: 60-150 VAC @ 40-70 Hz
  • 8 x NEMA 5-15R Total Outlets
  • 8 x Battery/Surge Protected Outlets
Built with a pre-installed RMCARD205 network management card that lets you remotely manage, monitor, and control your UPS using a standard web browser or network management system (NMS), the OL1500RTXL2UN Smart App Online UPS from CyberPower is a 2 RU rack/tower convertible device with double-conversion topology that provides battery backup and power protection via sine waveform output, plus surge protection for mission-critical enterprise servers, applications, network and storage devices, edge closets, PBX and VoIP installations, and more. The Extended Battery Module (EBM) expands runtime, and Fast Charge Technology restores full backup power faster. It comes equipped with an output capacity of 1500VA / 1350W, features an input voltage range of 60-150 VAC @ 40-70 Hz, and also has integrated circuitry for EMI/RFI filters. This Smart App UPS provides an integrated LCD panel for displaying real-time UPS vitals, such as the load/current level, runtime, battery level, temperature, input voltage, output voltage, battery in use, and more.
More Details
In Stock
No Store Display
Free Expedited Shipping
Protect Your Gear
Add a protection plan from $89.99
Ask an Expert
800-606-6969

CyberPower OL1500RTXL2UN Overview

Built with a pre-installed RMCARD205 network management card that lets you remotely manage, monitor, and control your UPS using a standard web browser or network management system (NMS), the OL1500RTXL2UN Smart App Online UPS from CyberPower is a 2 RU rack/tower convertible device with double-conversion topology that provides battery backup and power protection via sine waveform output, plus surge protection for mission-critical enterprise servers, applications, network and storage devices, edge closets, PBX and VoIP installations, and more. The Extended Battery Module (EBM) expands runtime, and Fast Charge Technology restores full backup power faster. It comes equipped with an output capacity of 1500VA / 1350W, features an input voltage range of 60-150 VAC @ 40-70 Hz, and also has integrated circuitry for EMI/RFI filters. This Smart App UPS provides an integrated LCD panel for displaying real-time UPS vitals, such as the load/current level, runtime, battery level, temperature, input voltage, output voltage, battery in use, and more.

When running a full load, this UPS can power devices for up to 3.4 minutes. When running a half load, it will last for up to 11 minutes. The OL1500RTXL2UN can be recharged up to 90% in around 4 hours and offers eight total NEMA 5-15R outlets, all of which are equipped with battery and surge protection and can absorb up to 1780 joules for keeping your devices safe against surges and spikes. Depending upon your needs, the outlets may also be configured as critical or non-critical, which allows for runtime prioritization for your devices. Other connections offered are a NEMA 5-15P input plug with a 10' cord, RS-323 serial, USB Type-B, Ethernet RJ45, and Phone RJ11.

This power supply is ENERGY STAR qualified with GreenPower UPS Bypass technology for reducing energy consumption and heat buildup to help save energy costs. Included with the power supply is the PowerPanel Business Edition UPS management software, which requires minimal system resources and monitors the status of the UPS to ensure it is working properly. When a power outage does occur, this software automatically saves open files and powers down the system into hibernation mode. When your PC is running in hibernation mode, the power supply will offer a longer runtime. This CyberPower UPS provides a lifetime connected equipment guarantee of up to $400,000.

Typical Applications
Enterprise servers
Network and storage devices
Edge closets
PBX and VoIP installations
Smart App Online 1-3KVA
General Features
Data Line Surge Protection
Data line surge protection helps prevents power surges that travel through telephone and Ethernet lines from causing damage to electronics.
Double-Conversion Topology
Provides consistent, clean power, regardless of the condition of the incoming power. Systems with this technology operate on isolated DC power 100% of the time and have a zero transfer time because they never need to switch to battery. Double-conversion UPS systems are designed for high-end system components, corporate servers, lab equipment, and other sensitive electronic devices.
Sine Wave Output
Provides power protection to ENERGY STAR 6.0 systems with Active PFC power supplies.
RMCARD205 Factory Installed
A full-featured network management card, the CyberPower RMCARD205 remotely manages, monitors, and controls CyberPower UPS systems via a standard web browser, command line interface (CLI), or network management system (NMS) connection.
LCD Control Panel
Displays UPS status data and configures operating settings from up to 10' away (DB26 cable not included). The LCD control panel displays and allows configuration of IP address settings when an RMCARD205 is installed.
Upgradeable UPS Firmware
The UPS firmware that manages the unit's features and functions is field upgradeable. UPS firmware upgrades require an RMCARD205 to be installed in the UPS and are done via the web management interface. The RMCARD205 must have firmware version 1.10 or above and UPS firmware must be Sv3A00 or above.
Extended Battery Module (EBM)
Extend runtime by adding EBMs. This UPS allows for up to ten added modules.
Fast Charge Technology
Allows UPS batteries to return to 100% capacity more rapidly by utilizing a built-in charger inside each EBM. Restores a complete charge within 5 hours regardless of the number of EBMs.
Smart Battery Management (SBM)
Improves and extends the functional life of a UPS battery and reduces excessive heat during work cycles by using a three-cycle charging process.
GreenPower UPS ECO Mode
Improves UPS efficiency up to 95% and saves on electrical and cooling costs.
Hot-Swappable Batteries
Eliminate downtime related to UPS power maintenance for continuous power availability.
Critical & Non-Critical Loads
The UPS has two banks of outlets which can be configured so that the non-critical loads shut off after a set timeframe to provide additional runtime for the critical load outlet. Users can prioritize their equipment runtimes to maximize the output of the UPS to meet their power requirements.
Emergency Power Off (EPO)
Allows the UPS to be shut off in the event of an emergency, when the EPO port is connected to an EPO switch.
Generator Compatible
Provides stable sine wave output (free of harmonics and distortion) without switching to battery mode when running on generator input power.
Converter Mode
Provides the flexibility to set the output frequency, regardless of the input frequency, to match connected equipment by selecting 50 Hz or 60 Hz output on the LCD control panel.
USB & Serial Connectivity
Enables full integration with built-in power management and auto shutdown features on Windows, Linux, and VMware systems through an HID-compliant USB port and Serial port.
EMI/RFI Filters
Prevent electromagnetic and radio frequency interference to help ensure clean power for connected equipment.
Audible Alarms
Identify when the model is running on battery power, overloaded, or has a low battery.
Resettable Circuit Breaker
Interrupts an electric current in a circuit when the current becomes too high.
LED Status Lights
Indicates Power On, Line Mode, Battery Mode, Bypass Mode, Fault, and Replace Battery.
Rack/Tower Versatility
Allows for horizontal rack or vertical tower installations.
PowerPanel Business Edition Software
Provides IT professionals with tools for monitoring and managing the UPS and backup power. This software offers remote management functionality and may downloaded for free from CyberPower's site.
Limited 3-Year Warranty
CyberPower will repair or replace a defective UPS system (including batteries) within three years of the purchase date.
Connected Equipment Guarantee
CyberPower will repair or replace properly connected equipment if it is damaged by a power surge.
UPC: 649532611782

CyberPower OL1500RTXL2UN Specs

Key Specs
Total Outlets
8x NEMA 5-15R
Plug Type
NEMA 5-15P
Surge Protection
Yes: 1780 Joules
Maximum Wattage
1350 W at 120 VAC
Full-Load Runtime
3.4 Minutes
General
Total Outlets
8x NEMA 5-15R
Protected Outlets
8x NEMA 5-15R (Battery and Surge)
Plug Type
NEMA 5-15P
Data Line Protection
RJ11, RJ45
Communications I/O
USB via USB-B
Serial via DE-9/DB-9
Emergency Power Off (EPO) Support
Yes
Topology
Double Conversion
Transfer Time
< 0 ms
Power
Surge Protection
Yes: 1780 Joules
Maximum Wattage
1350 W at 120 VAC
Input Voltage Range
60 to 150 VAC
Input Frequency
50/60 Hz ± 10 Hz (Auto Sensing)
Output Voltage Range
100 to 125 VAC
Output Frequency
50/60 Hz ± 0.25 Hz (Auto Sensing, Configurable)
Load Capacity
1500 VA
Thermal Dissipation
478 BTU/Hour
Maximum Efficiency
95%
Crest Factor
3:1
Power Factor Correction
0.9
Waveform
Sine Wave
Battery
Battery Capacity
(81 VaH)
Chemistry
Lead-Acid
Full-Load Runtime
3.4 Minutes
Half-Load Runtime
11 Minutes
Recharge Time
4 Hours
User Replaceable
Yes
Replacement Battery
RB1290X3L
Hot-Swap Support
Yes
Physical
Operating Conditions
32 to 104°F / 0 to 40°C up to 95% Humidity
Noise Level
38 to 55 dBA
Certifications
CSA, FCC, RoHS, UL
Cable Length
10' / 3.05 m
Material of Construction
Steel
Rackmount Size
2 U
Dimensions (W x H x D)
17.5 x 3.5 x 16.9" / 44.45 x 8.89 x 42.93 cm
Weight
39.6 lb / 17.96 kg
Packaging Info
Package Weight
53.55 lb
Box Dimensions (LxWxH)
22.35 x 21.5 x 9"