Vicon V1300X-IA-EX Alarm Interface (64 Inputs)

BH #VIV1300XIAEX • MFR #V1300XIAEX
Print
Vicon V1300X-IA-EX Alarm Interface (64 Inputs)
No Longer Available
No Store Display
Ask an Expert
800-952-1815

Vicon V1300X-IA-EX Overview

The V1300X-IA-EX Alarm Interface (64 Inputs) from Vicon is a product that allows external alarm devices to be connected to a Nova (VPS) digital control CPUs. Up to (64) alarms may be connected to this unit. Additional units may be cascaded for further expansion.

When this unit senses a change in the status of one of its alarm inputs, it transmits the data to the VPS CPU, which in turn alerts the operator. It may also be programmed to execute an automatic response, such as displaying video from a camera associated with the alarm, causing a camera station to carry out a preset program or tour, or playing special alarm messages on the monitors, among other options.

A single auxiliary relay output also activates when any alarm input goes active and may be used to control some external device such as a VCR or DVR. Alarm inputs are normally closed, but go active when the remote alarm switch opens or goes on active high. This unit's alarm inputs are CMOS/TTL compatible.

Enabling and disabling individual alarm inputs is managed with software in the system CPU. This unit is compatible with all Nova (VPS) CPUs except VPS238, which has its own alarm interface. It connects to the CPU via a parallel data interface.

External Alarms with Nova
This product allows external alarm devices to be connected to a Nova (VPS) digital control CPU.
Expansion
Additional units may be cascaded for further expansion.
Automatic Responses
This unit may be programmed to trigger automatic responses to alarms, such as switching to a camera or recording on an external VCR or DVR, among many other possibilities.
CMOS/TTL Compatible
This unit's alarm inputs are CMOS/TTL compatible.

Vicon V1300X-IA-EX Specs

Input
Alarm Inputs: x64 normally closed (NC) or TTL low
Output
Alarm Output: Signal sent to CPU when alarm input is detected
Auxiliary Output: Dry contact relay activates when alarm input is detected
Construction
Steel
Finish
Black, metal
Connectors
Alarm Inputs: x4 16-pin removable
Output to CPU: 37-pin D-shell connector
Aux Output: 3-pin removable screw terminal block
Power: Detachable 3-conductor cable with grounded plug
Indicators
Red LED on front panel
Power
Input Power:
64 inputs, 120V
Power Consumption:
15W
Heat Equivalent:
0.85 BTU/min (0.21 cal/min)
Input Signal:
Alarmed: Contacts open or active high
TTL high = 2.7 to 5.3 V
Secured: Contacts closed or active low
TTL low = 0.0 to 0.7 V
Auxiliary Relay:
Dry contact relay rated at: 1.0A at 24VDC or 0.5A at 115VAC
Fuse:
120V models: 0.75A, 250V, 5 mm
Radio-Frequency Emission Standard:
FCC Class A
European Community (CE) Standard:
EN 50081-1 generic emissions
EN 50082-1 generic immunity
Dimensions
3-1/2 x 19 x 7" (8.81 x 48.3 17.8cm)
Weight
9.0 lbs (4.1kg)