APC Smart-UPS Battery Backup & Surge Protector with SmartConnect

BH #APS3000RM2UC • MFR #SMT3000RM2UC
Print
APC Smart-UPS Battery Backup & Surge Protector with SmartConnect
Key Features
  • Output: 2700W / 2880 VA
  • Input: 120V @ 50/60 Hz ±3 Hz
  • 6 x NEMA 5-15R Battery Backup Outlets
  • 2 x NEMA 5-20R Battery Backup Outlets
Designed for servers, point-of-sale, routers, switches, hubs, and other network devices, the Smart-UPS Battery Backup with SmartConnect from APC delivers intelligent and efficient network power protection from entry level to scalable runtime. It can provide 395 minutes of use at 50W, 181 minutes of use at 100W, 99 minutes of use at 200W, 66 minutes of use at 300W, 49.1 minutes of use at 400W, 38.4 minutes of use at 500W, 31.2 minutes of use at 600W, 26 minutes of use at 700W, 22 minutes of use at 800W, 19 minutes of use at 900W, 16.5 minutes of use at 1000W, 12.9 minutes of use at 1200W, 10.3 minutes of use at 1400W, 8.3 minutes of use at 1600W, 6.8 minutes of use at 1800W, and 5.6 minutes of use at 2000W, 3.5 minutes of use at 2500W, and 2.8 minutes of use at its full load of 2700W.

This Smart-UPS features an output of 2700W / 2880 VA, an input of 120V @ 50/60 Hz ±3 Hz, six NEMA 5-15R and two NEMA 5-20R battery backup and surge outlets, a NEMA L5-30P input connection, a surge energy rating of 459 joules, line interactive topology, and a sine waveform. Included PowerChute Network Shutdown management software helps to provide unattended, yet proper shutdowns of network operating systems, and also included are rack-mounting support rails, rack-mounting hardware, an RS-232 cable, and a USB cable. Support is provided by a limited 3-year repair or replace warranty that excludes the battery, as well as a limited 2-year battery warranty and a limited lifetime $150,000 equipment protection policy.
More Details
In Stock
No Store Display
Free 2-Day Shipping
Protect Your Gear
Add a protection plan from $109.99
Ask an Expert
800-606-6969

APC SMT3000 Overview

Designed for servers, point-of-sale, routers, switches, hubs, and other network devices, the Smart-UPS Battery Backup with SmartConnect from APC delivers intelligent and efficient network power protection from entry level to scalable runtime. It can provide 395 minutes of use at 50W, 181 minutes of use at 100W, 99 minutes of use at 200W, 66 minutes of use at 300W, 49.1 minutes of use at 400W, 38.4 minutes of use at 500W, 31.2 minutes of use at 600W, 26 minutes of use at 700W, 22 minutes of use at 800W, 19 minutes of use at 900W, 16.5 minutes of use at 1000W, 12.9 minutes of use at 1200W, 10.3 minutes of use at 1400W, 8.3 minutes of use at 1600W, 6.8 minutes of use at 1800W, and 5.6 minutes of use at 2000W, 3.5 minutes of use at 2500W, and 2.8 minutes of use at its full load of 2700W.

This Smart-UPS features an output of 2700W / 2880 VA, an input of 120V @ 50/60 Hz ±3 Hz, six NEMA 5-15R and two NEMA 5-20R battery backup and surge outlets, a NEMA L5-30P input connection, a surge energy rating of 459 joules, line interactive topology, and a sine waveform. Included PowerChute Network Shutdown management software helps to provide unattended, yet proper shutdowns of network operating systems, and also included are rack-mounting support rails, rack-mounting hardware, an RS-232 cable, and a USB cable. Support is provided by a limited 3-year repair or replace warranty that excludes the battery, as well as a limited 2-year battery warranty and a limited lifetime $150,000 equipment protection policy.

APC SmartConnect makes the Smart-UPS more adaptable and easier to deploy, enabling you to view the status of your UPS through a secure web portal. Through this remote management interface, you'll receive automatic notifications, firmware updates, and advanced support.

SMT3000RM2UC
Adjustable Voltage Sensitivity
Provides the ability to adapt the UPS for improved performance in specific power environments or generator applications.
Adjustable Voltage-Transfer Points
Maximizes useful battery life by widening the input voltage window or tightening the output voltage regulation.
Audible Alarms
Provides notification of changing utility power and UPS power conditions.
Automatic Restart of Loads After UPS Shutdown
Automatically starts up the connected equipment upon the return of utility power.
Automatic Self-Test
Periodic battery self-test ensures early detection of a battery that needs to be replaced.
Battery Failure Notification
Provides early-warning fault analysis on batteries enabling timely preventive maintenance
Boost and Trim Automatic Voltage Regulation (AVR)
Gives higher application availability by correcting low and high voltage conditions without using the battery.
Disconnected Battery Notification
Warns when a battery is not available to provide backup power.
Energy Meter
Provides actual kilowatt hours of usage for energy conscious users.
Green Mode
Patent-pending operating mode that bypasses unused electrical components in good power conditions to achieve higher operating efficiency without sacrificing protection.
Hot-Swappable Batteries
Helps ensure clean, uninterrupted power to protected equipment while batteries are being replaced.
Intelligent Battery Management
Maximizes battery performance, life, and reliability through intelligent, precision charging.
Intuitive LCD Interface
Provides clear and accurate information in multiple languages with the ability to configure the UPS locally with user-friendly navigation keys.
LED Indicators
Provide easy-to-read status of the unit and utility power conditions.
Network Manageable
Provides remote power management of the UPS over the network.
Outlet Group Control
Turn on/off, reboot, or shut down select outlet groups to save dispatching technicians to remote locations.
Predictive Replace Battery Date
Dynamically provides the month and year when battery replacement is recommended to aide in long-term maintenance planning.
Pure Sine Wave Output on Battery
Simulates utility power to provide a high degree of compatibility for active PFC (power factor corrected) servers and sensitive electronics.
Sequenced Network Shutdown and Reboot
Customize network shutdown and reboot sequence of connected servers and UPSs.
Serial Connectivity
Provides management of the UPS via a serial port.
Sine Wave Output
Helps eliminate humming and heat generated when powering tubelights and fans.
Single Switched Outlet Group
Single outlet group that may be controlled separately from the UPS for discrete reboot of hung devices, sequenced on/off, and non-critical load shedding.
StruxureWare Data Center Expert Compatible
Enables centralized management via StruxureWare Data Center Expert.
Temperature-Compensated Battery Charging
Prolongs battery life by regulating the charge voltage according to battery temperature.
USB Connectivity
Provides management of the UPS via a USB port.
User-Replaceable Batteries
Increases availability by allowing a trained user to perform upgrades and replacements of the batteries, thus reducing the Mean Time to Repair (MTTR).
UPC: 731304331070

APC SMT3000 Specs

Key Specs
Total Outlets
6x NEMA 5-15R
2x NEMA 5-20R
Plug Type
NEMA L5-30P
Surge Protection
Yes: 459 Joules
Maximum Wattage
2700 W
Full-Load Runtime
2.8 Minutes
General
Total Outlets
6x NEMA 5-15R
2x NEMA 5-20R
Protected Outlets
6x NEMA 5-15R (Battery and Surge)
2x NEMA 5-20R (Battery and Surge)
Plug Type
NEMA L5-30P
USB Charging Ports
No
SmartSlot Interface
1
Coax Protection
No
Data Line Protection
RJ45
Communications I/O
USB via USB-A
Serial via RJ45
Emergency Power Off (EPO) Support
Yes
Noise Filtering
0.3%
Topology
Line Interactive
Transfer Time
6 to 10 ms
Power
Surge Protection
Yes: 459 Joules
Maximum Wattage
2700 W
Nominal Input Voltage
120 VAC
Input Voltage Range
82 to 144 VAC
Input Voltage Adjustable Range
75 to 154 VAC
Input Frequency
50/60 Hz ± 3 Hz (Auto Sensing)
Nominal Output Voltage
120 VAC
Output Frequency
60 Hz ± 3 Hz
Voltage Distortion
<5%
Load Capacity
2880 VA
Thermal Dissipation
348 BTU/Hour
Waveform
Sine Wave
Battery
Chemistry
Lead-Acid
Full-Load Runtime
2.8 Minutes
Half-Load Runtime
10.8 Minutes
Recharge Time
3 Hours
Number of Batteries
1
User Replaceable
Yes
Replacement Battery
RBC43
Hot-Swap Support
Yes
Physical
Operating Conditions
32 to 104°F / 0 to 40°C up to 95% Humidity
Noise Level
55 dBA
Certifications
CE
Cable Length
8' / 2.44 m
Rackmount Size
2 U
Dimensions (W x H x D)
18.9 x 3.4 x 26.9" / 48.01 x 8.64 x 68.33 cm
Weight
97.4 lb / 44.18 kg
Packaging Info
Package Weight
122 lb
Box Dimensions (LxWxH)
39 x 23.5 x 9.5"

APC SMT3000 Reviews

Fantastic

By Chris
Rated 5 out of 5
Date: 2023-01-27

Works exactly as advertised. Please note this is not a standard outlet type. 120v 30A locking barrel type. Please make sure you have the proper outlet on the wall. I did not and a surprise electrician expense to deal with. My own fault, the description is pretty clear, if not written in layman's terms.

Big boy does the job

By Gabriel
Rated 5 out of 5
Date: 2020-10-14

The front face buttons weren't quite as intuitive as I'd expected, but eventually you can figure it out. You will need to create an account with APC if you want to use the SmartConnect network cable. But the most important item of note - it is heavy! Lift with your knees, not your back. Better yet, buy a friend a (root) beer and get him/her/it to help you lift it.

See any errors on this page?

I just bought this and realized it came with a ...

I just bought this and realized it came with a 30amp AC Plug. Can I safely adapt this to 15amp plug to use in a regular outlet? Will it just result in a slower battery charge?
Asked by: erik
Thank you for your interest in our products. If you do change the input power cord to 15 amp it will derate the UPS to a 1500VA UPS. It wouldn't slow charge but you would not be able to connect the same amount equipment to the UPS. We do recommend a licensed electrician change out the cord as well. For more information on this please check out the following knowledge base. https://www.apc.com/us/en/faqs/FA156517/
Answered by: APCProductSupport
Date published: 2022-11-01

Hi, is this compatible with QNAP nas? I saw in a ...

Hi, is this compatible with QNAP nas? I saw in a youtube video the SMT750i but does that mean that this should work too?
Asked by: Turki
The APC Smart-UPS Battery Backup & Surge Pr tector with SmartConnect BH #APS3000RM2UC can be used with a NAS.
Answered by: Reuben K
Date published: 2023-07-23

Does this come with built in ethernet or do i ...

Does this come with built in ethernet or do i need to purchase an ethernet card?
Asked by: Chris
This BH #APS3000RM2UC does have a Ethernet(RJ45) port built in.
Answered by: Reuben K
Date published: 2022-07-25
  • y_2026, m_8, d_4, h_10CST
  • bvseo_bulk, prod_bvqa, vn_bulk_3.0.48
  • cp_1, bvpage1
  • co_hasquestionsanswers, tq_3
  • loc_en_US, sid_1384846, prod, sort_[SortEntry(order=HAS_STAFF_ANSWERS, direction=DESCENDING)]
  • clientName_bhphotovideo
Whatever You Need, We've Got It